The following are what we feel are the key points of the DD243 policy. This is not
a definitive list and should not be seen as the limit of an installation company's
responsibilities, merely as a guide to some of the main issues.
CONTENTS
Section 4 Primary design and configuration
considerations
- 4.1 Design Objectives
- 4.3 Transmission Fault Signals
Section 5
Design, installation and configuration of intruder alarm systems
- 5.4.1 Criteria for sequentially
confirmed alarm conditions
- 5.4.2 Configuration of movement
detectors that may offer a sequentially confirmed alarm
- 5.4.3 Configurations not regarded as
offering a sequentially confirmed alarm condition
Section 6
Other means of minimizing false alarms
Section 6
Other means of minimizing false alarms
6.2 Alarm
Filtering
All IASs must EITHER:
a) have the means to indicate to the ARC whether the IAS is set or
unset;
OR
b) be capable of generating a secondary signal identifiable at the ARC
as a mis-operation signal.
These requirements remain the same as under the NACP 14 and the previous DD243: 1999
document.
The filtering period (maximum 120 seconds as recommended in BS5979) will apply from the
first, unconfirmed activation and will continue to run even in the event of a second,
confirmed activation during the filtering period.
There are a series of conditions that mean that alarm filtering can be over-ridden. All
four must apply and these would only ever be effectively possible on some commercial
systems. The four conditions are:
1) Set/Unset monitoring in
use
2) Alarm at least 30 minutes after latest agreed setting time
3) Alarm at least 30 minutes before earliest agreed unsetting time
4) System set at least 15 minutes before alarm occurs
Top
6.3 Means of Completion of setting
The six permitted options for completion of
setting IASs are as follows:
a) Key operated shunt lock
fitted to final exit door
b) Push button switch mounted outside the protected premises
c) Protective switch (ie door contact) fitted to the final exit door
d) Portable ACE
e) In conjunction with an ARC
f) In the case of systems installed to comply with BS EN 50131, other
means.
The traditional timed exit method of setting
is now not allowed under DD243 unless the set period is completed by the means of a
push-to-set button or final door set using door contacts.
Other methods are now acceptable including completion of setting using portable ACE
(ancillary control equipment).
It is worth noting that means of COMPLETION of setting is not the same as means of
setting. For example a traditional end user code entered into a Remote Keypad (such as the
Pyronix MX-LCD) is acceptable, provided the completion of the setting procedure is by a
push-to-set button or by door contacts on the final exit door.
Where systems are installed to EN 50131, setting from outside the protected premises is
permitted.
Whatever method is chosen, there should be a time-limited indication to the user that the
setting has been completed. This may be audible i.e. the cessation of the exit tone.
Top
6.4 Means of unsetting
There are five options for means of unsetting under the DD243 policy.
a) Unlocking the initial
entry door unsets the IAS
b) Unlocking the initial entry door disables all means of confirmation
c) Opening the initial entry door disables all means of confirmation
d) Completion of unsetting is achieved using portable ACE
e) Unsetting is carried out in conjunction with an ARC
This section is possibly the one that will
have the biggest impact on many installation companies.
The traditional timed entry route, with the end user entering their code at a remote
keypad, is no longer acceptable.
Options (a) and (b) require an electrical connection between the lock and the IAS. For
example an electric lock or a shunt lock may be used. Electronic access control liked to
the IAS is also acceptable.
Option (c) is obviously the one that leaves greatest risk as a forced entry through the
entry door would disable confirmation! It is unlikely that this method of unsetting will
be acceptable to insurers for all risks. Furthermore, if this method is adopted the
installation company must advise the customer in writing that all confirmation is disabled
when the entry door is opened. They must also obtain, from the customer, in writing; that
this is acceptable.
Option (d) will allow the use of an entry timer in conjunction with portable ACE (such as
the Pyronix Prox) The portable ACE can be self-powered or can be in the form of a
proximity tag or card. It must be a single action device to unset the system (such as
presenting a tag or card to a proximity reader) and must offer security of no less than
that provided by a key switch of 1,000,000 differs.
Where a portable ACE is used however, there are points worth noting with regard to
confirmed alarms involving the entry route.
If the entry time expires without the IAS being unset, an unconfirmed alarm will be
signalled to the ARC. At that point the ARC will apply the alarm filtering delay.
If a detector off the entry route subsequently activates a further unconfirmed alarm will
be signalled to the ARC. Only on activation of a second, independent detector will a
confirmed alarm signal be able to be sent to the ARC.
Where detectors off the entry route activate during the entry time, it is considered
likely to be due to user error and these will not signal an alarm to ARC, but would cause
a local alarm.
Top |